7.5
Error handling
A check identifies available input signals after quitting the COMMIS
(commissioning) menu. We differentiate between two cases if one of the input
signals previously acquired is missing due to short-circuit or open circuit:
Case
Description
Display
1
At least 1 input signal is
missing, but calculation is still
possible.
Fault symbol
. The calculated values are
displayed (Info pictures and INFO menu
(Inputs/outputs)).
2
At least 1 input signal is
missing, and calculation is not
possible.
Fault symbol
.
Values according to the table below.
If calculation is not possible (case 2), the following
predefined values are displayed:
Calculation not possible
Function
Value
ENTH x
0 kJ/kg
ABSH x
0 g/kg
ENTH D
−
50 kJ/kg
DEWPNT 0
°C
The relevant input is not monitored later if one of the input signals is missing after
you quit the COMMIS (commissioning) menu.
See section 5.4 on how to handle input errors.
Note
30 / 46
Siemens
SEZ220 signal converter
CE1P5146en
Building Technologies
Function block ENTHALPY