12.5 Signal converter
DC 0…10 V signal to X1.
Task
Invert and output via Y2.
CONF / INPUT X1 / LABEL
%
Configuration
CONF / 2X-INV / IN X
X1
CONF / 2X-INV / AO 2
Y2
PARA / 2X-INV / INVERS2
YES
Setting value
12.6 Adapt signal
DC 0…10 V signal to X1.
Task
Adapt to DC 5…7.5 V range and output inverted to Y1.
CONF / INPUT X1 / LABEL
%
Configuration
CONF / 2X-INV / IN X
X1
CONF / 2X-INV / AO 1
Y1
PARA / 2X-INV / MINVAL1
0
Setting values
PARA / 2X-INV / MAXVAL1
100
PARA / 2X-INV / MINPOS1
50
PARA / 2X-INV / MAXPOS1
75
PARA / 2X-INV / INVERS1
YES
12.7 Signal doubler
DC 0…10 V signal to X1.
Task
Subdivide into ranges DC 0…5V (to Y1) and DC 5…10V (to Y2) with output as
active signals.
CONF / INPUT X1 / LABEL
%
Configuration
CONF / 2X-INV / IN X
X1
CONF / 2X-INV / AO 1
Y1
CONF / 2X-INV / AO 2
Y2
PARA / 2X-INV / MINVAL1
0
Setting values
PARA / 2X-INV / MAXVAL1
50
PARA / 2X-INV / MINPOS1
0
PARA / 2X-INV / MAXPOS1
100
PARA / 2X-INV / INVERS1
NO
PARA / 2X-INV / MINVAL2
50
PARA / 2X-INV / MAXVAL2
100
PARA / 2X-INV / MINPOS2
0
PARA / 2X-INV / MAXPOS2
100
PARA / 2X-INV / INVERS2
NO
42 / 46
Siemens
SEZ220 signal converter
CE1P5146en
Building Technologies
Application examples
02.06.2008