SITRANS TH/TR/TF
A5E32520700-01, 06/2013
27
Resistance transmitters
Table
7-2
Measured variable: Ohmic resistance
SITRANS TH200/TH300, TR200/TR300
SITRANS TH400
Input type
Resistance, potentiometer
Characteristic
Linear to resistance or special characteristic curve
Unit of measurement
Ω
Measuring range
Range
Min. span
Range
Resistance
0 ... 390
5
-
Resistance
0 ... 2200
25
0 ... 10000
Thermocouples
Table
7-3
Measured variable: Temperature
SITRANS TH200/TH300, TR200/TR300
SITRANS TH400
Sensor type (thermo pairs)
Range
Min. span
Range
●
Type B
Pt30Rh
-
Pt6Rh according to DIN
IEC 584
+100
...
+1820
(212 ... 3308)
100 (180)
+400
...
+1820
(752 ... 3308)
●
Type C
W5%
-
Re according to ASTM 988
0 ...
+2300
(32 ... 4172)
100 (180)
0 ...
+2300
(32 ... 4172)
●
Type D
W3%
-
Re according to ASTM 9
98
0 ...
+2300
(32 ... 4172)
100 (180)
0 ...
+2300
(32 ... 4172)
●
Type E
NiCr-
CuNi according to DIN IEC 584
-200 ...
+1000
(-328 ...
+1832)
50 (90)
-100 ...
+1000
(-148 ...
+1832)
●
Type J
Fe
-
CuNi according to DIN IEC 584
-210 ...
+1200
(-346 ...
+2192)
50 (90)
-100 ...
+1000
(-148 ...
+1832)
●
Type K
NiCr-
Ni according to DIN IEC 584
-230 ...
+1370
(-382 ...
+2498)
50 (90)
-100 ...
+1200
(-148 ...
+2192)
●
Type L
Fe
-
CuNi according to DIN 43710
-200 ...
+900
(-328 ...
+1652)
50 (90)
-200 ...
+900
(-328 ...
+165
2)
●
Type N
NiCrSi-
NiSi according to DIN IEC 584
-200 ...
+1300
(-328 ...
+2372)
50 (90)
-180 ...
+1300
(-292 ...
+2372)
●
Type R
Pt13Rh
-
Pt according to DIN IEC 584
-50 ...
+1760
(-58 ...
+3200)
100 (180)
-50 ...
+1760
(-58 ...
+3200)
●
Type S
Pt10Rh
-
Pt according to DIN IEC 584
-50 ...
+1760
(-58 ...
+3200)
100 (180)
-50 ...
+1760
(-58 ...
+3200)
●
Type T
Cu-
CuNi according to DIN IEC 584
-200 ...
+400
(-328 ...
+752)
40 (72)
-200 ...
+400
(-328 ...
+752)
●
Type U
Cu-
CuNi according to DIN 43710
-200 ...
+600
(-328 ...
+1112)
50 (90)
-200 ...
+600
(-328 ...
+1112)
Cold junction compensation
●
Internal
With integrated resistance thermometer Pt100
●
External
With external Pt100 IEC 60751 (two
-
wire or three
-
wire connection)
●
External fixed
Cold junction temperature can
be set as fixed value