SITRANS TH/TR/TF
16
A5E32520700-01, 06/2013
Table
4-3
For T
a
≤ 85
°C (T4); T
a
≤ 60
°C (T5); T
a
≤ 45
°C (T6)
Maximum values of the auxiliary power supply and signal circuits in accordance with FISCO:
U
i
= 17.5 V DC
I
i
= 250 mA
P
i
= 2000 mW
L
i
= 1 μH
C
i
= 2 nF
Table
4-4
For T
a
≤ 85
°C (T4); T
a
≤ 60
°C (T5); T
a
≤ 45
°C (T6)
Maximum values of the auxiliary power supply and signal circuits in accordance with FISCO:
U
i
= 15 V DC
I
i
= any
P
i
= any
L
i
= 1 μH
C
i
= 2 nF
Maximum values of the sensor circuit for Ex ia:
U
0
= 5.7 V DC:
I
0
= 8.4 mA
P
0
= 12 mW
L
0
[mH]
200
C
0
[μF]
40
Zone 1 in type of protection "ib"
-
intrinsic safety
●
Only connect the transmitter, in accordance with the certificate of compliance, to devices certified as intrinsically
-
safe.
●
The transmitter must be mounted in an enclosure in order to provide a degree of protection of at least IP20 according to
EN60529
Table
4-5
For T
a
≤ 85
°C (T4); T
a
≤ 75
°C (T5); T
a
≤ 60
°C (T6)
Maximum values of the auxiliary power supply and signal circuits:
U
i
= 30 V DC
I
i
= 250 mA
P
i
= 5320 mW
L
i
= 1 μH
C
i
= 2 nF
Table
4-6
For T
a
≤ 85
°C (T4); T
a
≤ 75
°C (T5); T
a
≤ 60
°C (T6)
Maximum values of the auxiliary power supply and signal circuits in accordance with FISCO:
U
i
= 17.5 V DC
I
i
= any
P
i
= any
L
i
= 1 μH
C
i
= 2 nF
Maximum values of the sensor circuit for Ex ia:
U
0
= 5.7 V DC:
I
0
= 8.4 mA
P
0
= 12 mW
L
0
[mH]
200
C
0
[μF]
40
Zone 2 in type of protection "nL/ic"
●
Install the transmitter in an enclosure meeting the degree of protection IP54 per EN 60529, e.g. in a type B connection
head per DIN 4372
9.
●
Only connect the transmitter to devices that have at least been approved as certified devices of Category 3.
●
Be sure to observe the respective values.
Table
4-7
For T
a
≤ 85
°C (T4); T
a
≤ 75
°C (T5); T
a
≤ 60
°C (T6)
Maximum values of the auxiliary power
supply and signal circuits:
U
i
= 32 V DC
I
i
= any
P
i
= any
L
i
= 1
μH
C
i
= 2 nF