background image

GENERAL DESCRIPTION 

      The GEMC-WL-WD2 is a 2-point window/door transmitter designed 

for use in Napco Gemini C-Series wireless systems, and with Napco's 
GEMC-RECV series wireless receivers (see WI1682).  When used 
with the supplied magnet, the transmitter functions as a window/door 
sensor.  Terminals are provided for supervised external contacts so 
that one or more additional contacts may be used in conjunction with, 
or instead of, the internal reed switch.  A jumper (J1) allows the use of 
external contacts (such as UL Listed door/window magnets or ball 
contacts, fire alarm pull stations, thermal detectors, waterflow tamper 

switches, etc.), instead of the internal reed switch within the same 
room (maximum 20' wire length for Burglary installations, maximum 3' 
wire length for Fire installations*; 22-18AWG) for Fire and Burglary 
sensors.  In addition, the GEMC-WL-WD2 includes a rear tamper to 
protect against the removal of the transmitter from the wall.   

      The GEMC-WL-WD2 is powered by a 3-volt lithium battery that will 

power the transmitter for up to 5 years.  When battery voltage drops 
below normal, a low-battery report will be sent to the receiver (replace 
battery with a Duracell 3V lithium battery DL123A, Varta/Power-One 
model CR123A or Panasonic CR123A only; use of another battery 
may present a risk of fire or explosion).   

      Each transmitter has a unique factory-programmed code (printed on 

the battery holder and also on the rear case) that distinguishes itself to 
the receiver.  (

Note:

 See control-panel instructions for entering this 

six-digit hexadecimal code and its checksum digit into the panel; be 
sure to enter all numbers and/or letters, including leading zeros, if 
any). 

      

Note: 

 When connected for use with a Fire system, and a fire condi-

tion sends a fire alarm signal, this signal will be sent until the condition 
clears.   

 

SPECIFICATIONS 

Electrical Ratings 
Input Power:  

Powered by a 3-volt lithium battery.  Two zone inputs. 

Loop voltage:  

3V nominal 

180K End of line resistor part #: 

 EOL180K (for loop 1 only) 

GEMC-WL-WD2 

Commercial / Residential Window / Door Transmitter  

with Rear Tamper 

INSTALLATION INSTRUCTIONS 

WI1743B  08/10 

R

333 Bayview Avenue 

Amityville, New York 11701 

For Sales and Repairs, (800) 645-9445 

For Technical Service, (800) 645-9440 

 

 

Publicly traded on NASDAQ     Symbol: NSSC

 

© NAPCO 2010 

      Use only one device when used with Fire initiating devices.   

Maximum Zone Wiring Length:  

20 feet maximum for Burglary in-

stallations, 3 feet maximum for Fire installations* (#18-22 AWG) 

Maximum Loop Resistance:

  300 ohms 

Operating Frequency: 

 319.5Mhz 

Maximum Distance from Receiver: 

 Up to 1000 feet, depending on 

local environment 

 

INSTALLATION 

      Note:   

The transmitter and magnet may be mounted in any position 

with no degradation in performance.  Thus, if a left-handed reed 
switch is required, the unit may be mounted upside down.  However, 
for reference purposes in this text, the transmitter will be considered 
oriented with the antenna at the top, as shown in these illustrations. 
1.  

Remove the cover.  

Remove the GEMC-WL-WD2 transmitter 

cover by inserting a small screwdriver into the slot at the bottom 
and twisting while applying upward pressure.  See Fig. 2 below. 

2.  

Insert the battery.  

Observe battery polarity.  Insert battery with 

positive (+) terminal toward terminal block.  See Fig. 3.  The 
battery will not make contact if inserted backwards. 

3.  

Identify transmitter parts.  

Refer to Fig. 4. 

4.  

Select transmitter location.  

Avoid mounting the transmitter near 

the floor.  Low level mounting can reduce transmission range and 
may subject the transmitter to damage. 

5.  

Remove transmitter and magnet mounting plates. 

 

Transmitter: Use a small screwdriver to push in retaining tab (Fig. 
6) and slide cover upward.  Magnet: Insert small screw driver into 
slot at either end of magnet cover.  Push in and twist to pop off 
cover.  If using external contacts, skip to Step 7. 

6.  

Attach mounting plates.  Note:

 While use of the transmitter 

mounting plate is recommended, mounting holes in the rear case 
allow mounting without the plate.  Use #6 flat-head screws to affix 
the mounting plates, observing alignment marks shown in Fig. 6.  
Mount the magnet within ½" from the transmitter.  Place the tam-
per spring that emerges from the transmitter rear cover into the 
top of the oval hole in the transmitter mounting plate.  Move the 
transmitter down until it snaps onto its mounting plate; snap the 
magnet onto its mounting plate.  For internal contacts, skip to Step 
9. 

7.  

(For external contacts only).  

Install contact or sensor and 

transmitter mounting plate (if used).  Mount the external contact or 
sensor as described in its instructions.  For recessed wiring, drill 
an access hole for the wire. 

8.  

(For external contacts only).  

Connect to terminals.  Connect 

two wires from an external sensor having normally-closed 
contacts (or a normally-closed loop) to Point-1 (Terminals 1–2).  
Similarly, if required, connect a sensor (or loop) to Point-2 
(Terminals 2–3). 

9.  

Complete transmitter setup.  

Install Jumper J2 (see Fig. 4) to 

enable the holdoff timer (after triggering, unit waits 3 minutes 
before retriggering).  For example, if used on doors in heavy traffic 
areas, this will prevent multiple alarms and thus conserve battery 
life.  

Note:

  If J2 is installed, both points will be delayed 3 minutes 

before retriggering.  If internal reed switch is used, remove Jumper 
J1 (see Fig. 4) and short Point-1 (Terminals 1–2).  An external 
contact may be connected to point 2. 

10. 

Close the transmitter case.  

Close the case by engaging the 

hooks at the top, then snap the bottom together. 

11. 

Program the panel.  

Enter (a) the zone number to which the 

transmitter will be mapped; (b) the 6-digit ID code with checksum 
digit; and (c) the wireless point number.  Refer to the programming 
instructions for the control panel and keypad in use.  

Note: 

In UL 

burglary installations, program the burglary alarm output for all 
protective devices. 

Fig. 1.  GEMC-WL-WD2 Component Parts 

 

REAR COVER 

 

MOUNTING PLATE 

MOUNTING PLATE 

FRONT COVER 

MAGNET 

TRANSMITTER 

PC BOARD 

FRONT COVER 

(R

ET

AI

N

IN

G

 T

A

B

Fig. 3.  Installing the battery 

Fig. 2.  Open the case 

 

 

1. Push up 
2. Twist 

*In Fire installations, leads extending from the GEMC-WL-WD2 located within 
7 feet of the floor must be run inside the wall or protected by conduit, etc. 

Reviews: