Remote operation
7.1 Operating via SIMATIC PDM
SITRANS LR250 (PROFIBUS PA)
Operating Instructions, 08/2014, A5E32221386-AC
93
1.
Open the menu Device – Simulation, and select the desired function block.
2.
Click on the tab Simulation (Measured value).
3.
Enable simulation, enter a percentage value, set the desired quality and status, and click on
Transfer. See Status Byte (Page 269) for more information on status and quality.
4.
The Output value from the desired function block is displayed in PDM, and the LCD displays
the substitute value. See Simulate Output below, to set the output mode.
5.
After simulation is complete, disable simulation and click on Transfer.