Parameter reference
SITRANS LR250 (PROFIBUS PA)
158
Operating Instructions, 08/2014, A5E32221386-AC
Security (6.)
Note
Default settings in the parameter tables are indicated with an asterisk (*) unless explicitly
stated.
Remote Access (6.1.)
Remote Lockout (6.1.1.)
Note
If access control is changed to limit remote access, it can be reset only via the handheld
programmer.
Enables or disables programming via the network and PDM.
Options
* OFF (Remote operation enabled)
ON (Remote operation disabled)
Local Access (6.2.)
Write Protection (6.2.1.)
Note
Do not lose this number value.
Prevents any changes to parameters via PDM or the hand-held programmer.
Hand-held
programmer values
Range: 0 to 99999. Default: Off
2457 (unlock value)
Off (enables programming)
any other value
On (disables programming)