Connecting
5.2 Connecting SITRANS LR250
SITRANS LR250 (PROFIBUS PA)
44
Operating Instructions, 08/2014, A5E32221386-AC
Note
•
PROFIBUS PA cable shield must be terminated at both ends of the cable for it to work
properly.
•
If a Weidmüller or other current limiting junction box is connected to this device, please
ensure that the current limit is set to 40 mA or higher.
•
Please refer to the PROFIBUS PA User and Installation Guidelines (order number 2.092)
for information on installing PROFIBUS devices at:
PROFIBUS PA (
Basic PLC configuration with PROFIBUS PA
①
Active PLC
④
DP/PA coupler
②
PROFIBUS DP
⑤
PROFIBUS PA
③
PC/laptop
⑥
SITRANS LR250 (PROFIBUS PA)