Parameter reference
SITRANS LR250 (PROFIBUS PA)
116
Operating Instructions, 08/2014, A5E32221386-AC
Vessel Shape
LCD DISPLAY/ Description Also required
HALF SPHERE BOT/
Half-sphere bottom
Maximum volume,
dimension A
FLAT SLOPED BOT/
Flat sloped bottom
Maximum volume,
dimension A
PARABOLIC ENDS/
Parabolic end horizontal
cylinder
Maximum volume,
dimension A, dimension
L
LINEAR TABLE
a)
/
Linearization table
(level/volume breakpoints)
Maximum volume,
tables 1-32 level and
volume breakpoints
a)
Linearization Table must be selected in order for level/volume values [see XY
index (2.4.1.5.)] to be transferred.
Maximum Volume (2.4.1.2.)
The maximum volume of the vessel. Units are defined in PV Units (volume/ level) (2.3.3.). Enter
the vessel volume corresponding to High Calibration Point. The volume calculation is based on
the maximum volume and scaled according to the vessel shape selected. If no vessel shape is
entered, the default is 100, and the reading will be a percentage value.
Values
Range: 0.0000 to 999999
Default: 100.0
Related Parameters Low Calibration Pt. (2.3.7.1.)
High Calibration Pt. (2.3.7.2.)
Vessel Shape (2.4.1.1.)
For readings in volumetric units instead of percentage values:
1.
Select a volumetric unit from PV Units (volume/level) (2.3.3.).
2.
Enter the vessel volume corresponding to High Calibration Point.