Safety notes
2.4 Certificates
MAG 6000 I / MAG 6000 I Ex de transmitter
18
Operating Instructions, 04/2016, A5E02083319-AG
2.3.3
FM Class I, II, III, Div 1 approval
Compact version for MAG 3100/3100 P sensors DN 15 to 300 (½" to 12")
Hazardous area
Class I, Div. 1, Group A, B, C, D
User I/O interface
Passive current
(31, 32)
Active current
(31, 32)
Relay
(44, 45, 46)
Frequency/pulse
(56, 57)
Profi (FISCO)
(95, 96)
Digital input
(77, 78)
ABCD
CD
AB
ABCD
ABCD
ABCD
ABCD
U
i
28 V DC U
O
30 V DC
30 V DC
U
i
30 V DC U
i
28 V DC U
i
17.5 V DC
U
i
30 V DC
I
I
100 mA
I
O
87.8 mA
86.8 mA
I
I
200 mA
I
I
100 mA
I
I
380 mA
I
I
C
I
19.7 nF
C
O
557 nF
63 nF
C
I
3.3 nF
C
I
14.2 nF
C
I
0 nF
C
I
0 nF
L
I
36 µH
L
O
18.4 mH
4.6 mH
L
I
0 µH
L
I
36 µH
L
I
0 µH
L
I
0 µH
P
I
0.7 W
P
O
0.66 W
0.66 W
P
I
1.2 W
P
I
1.2 W
P
I
5.32 W
P
I
1.2 W
Notes from control drawing
1.
The non-intrinsically safe terminals (power rail) must not be connected to a device which
uses or generates more than 250/30 Vrms or DC.
2.
The installation must meet the requirements of the National Electrical Code/Canadian
Electrical Code.
3.
Conduit seal is required within 460 mm (18") from MAG 6000 I in hazardous areas
(Class I, Div. 1).
The control drawings are found on the CD-ROM shipped with the device and on the Siemens
homepage at http://www.siemens.com/flowdocumentation.