Safety notes
2.3 Installation in hazardous area
MAG 6000 I / MAG 6000 I Ex de transmitter
14
Operating Instructions, 04/2016, A5E02083319-AG
Compact transmitter version:
●
Ex d e [ia] ia IIC T3-T6 Gb
Ex tD A21 IP67 T** °C (** pipe tempe5K, but not less than T85 °C
(MAG 3100 / MAG 3100 P)
●
Ex d e [ia] ia IIB T3-T6 Gb
Ex tD A21 IP67 T** °C (** pipe tempe18K, but not less than T85 °C
(MAG 1100 / MAG 1100 F)
For sensors:
Refer to sensor certificates:
MAG 3100 / MAG 3100 P: Sira 07ATEX1182X (DN 15-DN300); Sira 03ATEX3339X (DN350-
DN2000)
MAG 1100 / MAG 1100 F: Sira 07ATEX3181X
Safety parameters associated with the remote transmitter version
Table 2- 1
Intrinsically safe data
Sensor electrode input (Terminals 0, 81, 82, 83, 84 - "ia circuits")
IIB
IIC
U
O
30 V DC
30 V DC
I
O
6.1 mA
6.1 mA
C
O
560 nF
66 nF
L
O
1 H
0.96 H
P
O
45.5 mW
45.5 mW
Sensor coil terminals
Terminal type
85 and 86
"e"
Power supply:
Parameter
MAG 6000 I Ex de
Supply
115 to 230 VAC or 18 to 30 VDC
Max. allowable supply voltage U
m
(according to
ATEX certificate)
264 V
Ambient temperature
-20 to +60 °C (-4 to 140 °F)
Enclosure
IP67 / NEMA 4X
Summary of Contents for SITRANS F MAG 6000 EX DE