Procedure
1. Plug in an empty and fat32 formatted USB stick into your PC.
For USB stick specifications see cahpter Technical specifications SITRANS CC220 (Page 69).
2. Create a file named “ConBox_Commands.json” directly on the USB stick.
3. Open the “ConBox_Commands.json” file in a text editor.
4. Enter the following USB command:
{
"Commands": [
{
"Cmd":"CopyArchivedLogsToUsbStick",
"DeleteAfterCopy":"false"
}
]
}
5. Save the changes to the "ConBox_Commands.json".
6. Plug your USB stick into the USB Port of SITRANS CC220.
⇒ If the log file is big, the USER LED flashes slowly orange while the log files are been copied
to the USB stick.
If the log file is very small, the copy process is short and the LED flashing will not be seen. The
log file is small, if you have recorded half a day.
7. Remove the USB stick from SITRANS CC220.
8. Send the log files to the Technical support (Page 76).
9. Before you establish a connection of SITRANS CC220 to SITRANS SCM IQ again (Onboarding),
remove the "ConBox_Commands.json" file from the USB stick.
See also
Meaning of the LED states on SITRANS CC220 (Page 67)
Service and maintenance
9.1 Maintenance and repair work for SITRANS CC220
Smart Condition Monitoring with IIoT Sensors
Operating Instructions, 08/2021, A5E50573389-AA