7.3
Administrating the network for SITRANS CC220
Required user role
Network administrator of your side.
Procedure
1. Consider the choice of your network settings in SITRANS SCM IQ (Page 41) according to your
network policies ("DHCP" or "Static IP").
2. Make sure the UDP port 123 is accessible in the network.
SITRANS CC220 is using Siemens NTP server pool: {0..3}.siemens.pool.ntp.org. NTP time
synchronization is using UDP port 123.
7.4
Powering up SITRANS MS200
WARNING
Removing the lid in a dirty environment
Do not remove the lid in a dirty environment, as contamination of internal components could
reduce battery life.
• Remove the lid only in an environment of approximately 25 °C (77 °F) and 30-60% RH.
WARNING
Electrostatic discharge
• Prevent grease or other contaminants from touching PCB, as this could reduce battery life.
• Avoid direct skin contact with PCB.
Commissioning
7.4 Powering up SITRANS MS200
Smart Condition Monitoring with IIoT Sensors
38
Operating Instructions, 08/2021, A5E50573389-AA