Commissioning
6.2 Empty Pipe Set
FUE1010 IP65 NEMA 4X
Operating Instructions, 12/2014, A5E03086491-AC
89
6.
Press the <Right Arrow> and then <ENTER> to save the site data.
7.
The flow meter is now ready to report flow.
Note
Refer to Appendix A I/O Connections and Wiring (Page 173) tables for input/output wiring
for data spanning procedures.
6.2
Empty Pipe Set
The flow meter performs the MTYmatic routine automatically during its Initial Make-up to
establish a standard setting for the Empty Pipe alarm. This process is normally sufficient for
setting this parameter. The [Empty Pipe Set] option list allows you to re-invoke MTYmatic,
use an Actual MTY routine (if application conditions allow you to empty and refill the pipe) or
use the Set Empty routine to set the empty pipe threshold by direct numeric entry.
Actual MTY Command
If application conditions allow you to empty and refill the pipe, then you may choose to
perform the Actual Empty procedure; however, it is not required to do so.
NOTICE
IMPORTANT
NEVER perform the Actual MTY procedure if the pipe can not be emptied.
To use the Actual MTY command:
1.
From [Channel Setup] scroll down to [Install Sensor].
2.
Press the <Right Arrow> to access the [Empty Pipe Set] option list.
Summary of Contents for SITRANS 7ME3500
Page 2: ......
Page 213: ......
Page 214: ......
Page 215: ......
Page 216: ......
Page 217: ......
Page 218: ......
Page 219: ......
Page 220: ......
Page 221: ......
Page 222: ......
Page 223: ......
Page 224: ......
Page 225: ......
Page 226: ......
Page 227: ......
Page 228: ......
Page 229: ......
Page 230: ......
Page 231: ......
Page 232: ......
Page 233: ......
Page 234: ......
Page 235: ......
Page 236: ......
Page 237: ......
Page 238: ......
Page 239: ......
Page 240: ......
Page 241: ......
Page 242: ......
Page 243: ......
Page 244: ......
Page 245: ......
Page 246: ......
Page 247: ......
Page 248: ......
Page 249: ......
Page 250: ......
Page 251: ......
Page 252: ......
Page 253: ......
Page 254: ...21614 C 1011NFPS 7 ...
Page 255: ...1011NFPS 7 C 21614 ...
Page 256: ...1011NFPS 7 C 21614 ...
Page 257: ...21614 C 1011NFPS 7 ...
Page 258: ......
Page 259: ......
Page 260: ......
Page 261: ......
Page 262: ......
Page 263: ...21614 C ...
Page 264: ......
Page 265: ......
Page 266: ...1012TN 7 INSTALLATION DRAWING 1010 SERIES TRANSDUCERS AND MOUNTING TRACKS 21614 C ...
Page 267: ...1012TN 7 INSTALLATION DRAWING 1010 SERIES TRANSDUCERS AND MOUNTING TRACKS 21614 C ...
Page 268: ...1012TNH 7 INSTALLATION DRAWING 1010 SERIES TRANSDUCERS AND MOUNTING TRACKS 21614 C ...
Page 269: ...1012TNH 7 INSTALLATION DRAWING 1010 SERIES TRANSDUCERS AND MOUNTING TRACKS 21614 C ...
Page 270: ......
Page 271: ......
Page 272: ......
Page 273: ......
Page 274: ......
Page 275: ......
Page 276: ...21614 C STEP 4 BAND LENGTH TABLE PERMANENT INSTALLATION SERVICE NOTE STEP 2 STEP 3 STEP 1 ...
Page 277: ......
Page 278: ......
Page 279: ......
Page 280: ......
Page 282: ......
Page 290: ...Glossary FUE1010 IP65 NEMA 4X 216 Operating Instructions 12 2014 A5E03086491 AC ...
Page 294: ...Index FUE1010 IP65 NEMA 4X 220 Operating Instructions 12 2014 A5E03086491 AC ...
Page 295: ......