Alternative time setting
If an NTP server IP address has not been configured or a server was not found on the network,
you can also set the time of day using the following options:
• SIRIUS Soft Starter ES (TIA Portal) Premium / Professional via 3RW5 communication module
Brief overview: Window "Project Navigation" with current project under created Soft Starter >
"Commissioning" > Window "Working area" > "Soft Starter > Functions > Time"
• SIRIUS Soft Starter ES (TIA Portal) via local interface on the 3RW5 HMI High Feature
Brief overview: See SIRIUS Soft Starter ES (TIA Portal) Premium / Professional
via 3RW5 communication module
• 3RW5 HMI High Feature
Menu: "Parameter > Soft starter > Date & Time"
You will find more information on operating the 3RW5 HMI High Feature in the Equipment
Manual of the 3RW5 soft starter.
8.3
Web server
Requirement
• 3RW5 PROFINET High Feature communication module from firmware version V2.0
• Soft starter 3RW55 with firmware version V2.1.1 or higher or soft starter 3RW55 Failsafe with
firmware version V1.1.0 or higher
• PC or programming device with web browser (Page 93)
Principle of operation
With the web server, the 3RW5 PROFINET High Feature communication module offers you the
possibility to retrieve information from the 3RW55 and 3RW55 Failsafe soft starters from a PC or
programming device using a web client. The 3RW5 PROFINET High Feature communication
module provides all information and data in the form of web pages (html pages).
To be able to control 3RW55 or 3RW55 Failsafe soft starters via the web server (Page 96), you
must be logged on (Page 98) with a user account ("Operator" or "Maintenance personnel" user
role) via a secure https connection. For more information on user account management, refer
to the 3RW55 and 3RW55 Failsafe Soft Starters Equipment Manual. All other functions are
possible without logon.
If you control the 3RW55 or 3RW55 Failsafe soft starter via the web server, the 3RW5 soft starter
is in the operating mode "Manual operation bus - Webserver controlled" (Page 24).
Web pages
• Home
• Overview
• Faults and warnings
• Current status
Functions
8.3 Web server
SIRIUS 3RW5 PROFINET communication modules
92
Equipment Manual, 05/2021, A5E35631297002A/RS-AD/004