A.4.3
Commands
A.4.3.1
Data set 93: Commands
Only write (w) access to the command is possible.
Byte
Data format
Meaning
3RW
50
1)
52
2)
55 /
55‑F
3)
0
Unsigned8
Coordination
[0x21] Write via acyclic bus channel – user program
x
x
x
2
Unsigned8
Slot number
x
x
x
4
Unsigned8
Number of commands
x
x
x
5
Unsigned8
Command 1
x
x
x
6
Unsigned8
Command 2 (optional)
x
x
x
7
Unsigned8
Command 3 (optional)
x
x
x
8
Unsigned8
Command 4 (optional)
x
x
x
9
Unsigned8
Command 5 (optional)
x
x
x
1)
Supported by SIRIUS 3RW50 soft starter
2)
Supported by SIRIUS 3RW52 soft starter
3)
Supported by SIRIUS soft starter 3RW55 and 3RW55 Failsafe
The coding of the commands is described in the following table:
Code
Command
3RW5
50 /
52
1)
55
2)
55‑F
3)
0
No function
x
x
x
1
Reset
w
w
w
2
Enable Emergency start
-
w
w
3
Disable Emergency start
-
w
w
4
Automatic mode
w
w
w
5
Manual operation
w
w
w
6
Factory settings
w
w
w
7
Reset maximum pointer
w
4)
w
w
9
Restart
w
w
w
20
Delete logbook application - error
w
w
w
22
Delete logbook application - warning
-
w
w
24
Delete logbook application - events
-
w
w
42
Enable Emergency run
-
w
5)
-
43
Disable Emergency run
-
w
5)
-
44
Activate simulation
-
w
6)
-
45
Deactivate simulation
-
w
6)
-
46
Activate test with small load
w
4)
w
w
47
Deactivate test with small load
w
4)
w
w
Appendix
A.4 Data sets
SIRIUS 3RW5 PROFINET communication modules
160
Equipment Manual, 05/2021, A5E35631297002A/RS-AD/004