6.2.1
Configuring the 3RW5 Soft Starter in the PROFINET IO system
6.2.1.1
Configuring 3RW5 soft starters without assistance from a 3RW5 HMI High Feature
This section describes a possible configuration of the 3RW5 soft starter which you can only carry
out via the configuration software of the controller. You do not need a 3RW5 HMI High Feature
for this configuring option.
Requirements
• Connection of the 3RW5 soft starter via PROFINET
• Supply voltage (control supply voltage) switched on at 3RW5 soft starter
• MAC address
You can read the MAC address on the front of the 3RW5 communication module.
Procedure
①
Programmable logic controller/IO controller, e.g. SIMATIC S7‑1500
②
PC or programming device with configuration software of controller
③
PROFINET
④
SIRIUS 3RW5 soft starter / IO device
...
: Steps to be taken in the procedure
Configuring
6.2 Configuring the 3RW5 Soft Starter
SIRIUS 3RW5 PROFINET communication modules
Equipment Manual, 05/2021, A5E35631297002A/RS-AD/004