Procedure
1. Make sure that the motor is switched off and that you do not start the motor while restoring
the factory settings.
To ensure the quickest and most fault-free restoration of the factory setting, it is
recommended that you disconnect the main voltage (operating voltage) at the 3RW5 soft
starter.
2. Restore the factory settings.
The following procedures are possible via the 3RW5 communication module:
– Via the configuration software of controller (e.g. STEP 7) on the 3RW5 communication
module. Only the communication parameters are reset here.
– Via SIRIUS Soft Starter ES (TIA Portal) Premium / Professional on the 3RW5 communication
module
Brief overview: Window "Project Navigation" with current project under created Soft
Starter > "Commissioning" > Window "Work area" > "Soft Starter > Functions >
Commands > Factory settings"
Brief overview: Window "Project Navigation" with current project under created Soft
Starter > "Online & Diagnostics" > Window "Work area" > "PROFINET IO ST /
PROFINET IO HF > Functions > Reset to factory settings"
– Via data set 93 (Page 160) with the command "Factory settings"
Other possibilities for restoring the factory settings
Additional information on restoring the factory setting via the 3RW5 soft starter, via the
3RW5 HMI High Feature or via the SIRIUS Soft Starter ES (TIA Portal) on the local interface on the
3RW5 HMI High Feature can be found in the 3RW5 Soft Starter Equipment Manual.
Result
The factory setting of the selected device or all devices is restored.
Maintenance and service
9.3 Restoring factory settings
SIRIUS 3RW5 PROFINET communication modules
144
Equipment Manual, 05/2021, A5E35631297002A/RS-AD/004