![Siemens SIPROTEC 7SJ62 Manual Download Page 651](http://html.mh-extra.com/html/siemens/siprotec-7sj62/siprotec-7sj62_manual_382149651.webp)
Appendix
A.8 Settings
SIPROTEC, 7SJ62/64, Manual
C53000-G1140-C207-2, Release date 01.2008
651
9056
RTD 5 STAGE 2
RTD-Box
-58 .. 482 °F;
∞
248 °F
RTD 5: Temperature Stage 2
Pickup
9061A
RTD 6 TYPE
RTD-Box
Not connected
Pt 100
Ω
Ni 120
Ω
Ni 100
Ω
Not connected
RTD 6: Type
9062A
RTD 6 LOCATION
RTD-Box
Oil
Ambient
Winding
Bearing
Other
Other
RTD 6: Location
9063
RTD 6 STAGE 1
RTD-Box
-50 .. 250 °C;
∞
100 °C
RTD 6: Temperature Stage 1
Pickup
9064
RTD 6 STAGE 1
RTD-Box
-58 .. 482 °F;
∞
212 °F
RTD 6: Temperature Stage 1
Pickup
9065
RTD 6 STAGE 2
RTD-Box
-50 .. 250 °C;
∞
120 °C
RTD 6: Temperature Stage 2
Pickup
9066
RTD 6 STAGE 2
RTD-Box
-58 .. 482 °F;
∞
248 °F
RTD 6: Temperature Stage 2
Pickup
9071A
RTD 7 TYPE
RTD-Box
Not connected
Pt 100
Ω
Ni 120
Ω
Ni 100
Ω
Not connected
RTD 7: Type
9072A
RTD 7 LOCATION
RTD-Box
Oil
Ambient
Winding
Bearing
Other
Other
RTD 7: Location
9073
RTD 7 STAGE 1
RTD-Box
-50 .. 250 °C;
∞
100 °C
RTD 7: Temperature Stage 1
Pickup
9074
RTD 7 STAGE 1
RTD-Box
-58 .. 482 °F;
∞
212 °F
RTD 7: Temperature Stage 1
Pickup
9075
RTD 7 STAGE 2
RTD-Box
-50 .. 250 °C;
∞
120 °C
RTD 7: Temperature Stage 2
Pickup
9076
RTD 7 STAGE 2
RTD-Box
-58 .. 482 °F;
∞
248 °F
RTD 7: Temperature Stage 2
Pickup
9081A
RTD 8 TYPE
RTD-Box
Not connected
Pt 100
Ω
Ni 120
Ω
Ni 100
Ω
Not connected
RTD 8: Type
9082A
RTD 8 LOCATION
RTD-Box
Oil
Ambient
Winding
Bearing
Other
Other
RTD 8: Location
9083
RTD 8 STAGE 1
RTD-Box
-50 .. 250 °C;
∞
100 °C
RTD 8: Temperature Stage 1
Pickup
9084
RTD 8 STAGE 1
RTD-Box
-58 .. 482 °F;
∞
212 °F
RTD 8: Temperature Stage 1
Pickup
9085
RTD 8 STAGE 2
RTD-Box
-50 .. 250 °C;
∞
120 °C
RTD 8: Temperature Stage 2
Pickup
9086
RTD 8 STAGE 2
RTD-Box
-58 .. 482 °F;
∞
248 °F
RTD 8: Temperature Stage 2
Pickup
9091A
RTD 9 TYPE
RTD-Box
Not connected
Pt 100
Ω
Ni 120
Ω
Ni 100
Ω
Not connected
RTD 9: Type
9092A
RTD 9 LOCATION
RTD-Box
Oil
Ambient
Winding
Bearing
Other
Other
RTD 9: Location
9093
RTD 9 STAGE 1
RTD-Box
-50 .. 250 °C;
∞
100 °C
RTD 9: Temperature Stage 1
Pickup
9094
RTD 9 STAGE 1
RTD-Box
-58 .. 482 °F;
∞
212 °F
RTD 9: Temperature Stage 1
Pickup
9095
RTD 9 STAGE 2
RTD-Box
-50 .. 250 °C;
∞
120 °C
RTD 9: Temperature Stage 2
Pickup
Addr.
Parameter
Function
C
Setting Options
Default Setting
Comments
www
. ElectricalPartManuals
. com