Mounting and Commissioning
3.1 Mounting and Connections
SIPROTEC, 7SJ62/64, Manual
C53000-G1140-C207-2, Release date 01.2008
431
3.1.3
Installation
3.1.3.1
Panel Flush Mounting
Depending on the version, the device housing can be
1
/
3
,
1
/
2
or
1
/
1
. For housing size
1
/
3
or
1
/
2
(Figure 3-24 and
Figure 3-25) 4 covers and 4 holes for securing the device, for housing size
1
/
1
(Figure 3-26) there are 6 covers
and 6 holes for securing the device.
• Remove the 4 covers at the corners of the front cover, for size
1
/
1
the 2 covers located centrally at the top
and bottom have to be removed as well. Thereby the 4 and 6 oblong holes in the mounting flange respec-
tively can be accessed.
• Insert the device into the panel cut-out and fasten it with four or six screws. For dimensions refer to Section
• Put the 4 or six covers back in place.
• Connect the ground on the rear plate of the device to the protective ground of the panel using at least one
M4 screw. The cross-sectional area of the ground wire must be equal to the cross-sectional area of any other
control conductor connected to the device. The cross-section of the ground wire must be at least 2.5 mm
2
.
• Connections are realized via the plug or screw terminals on the rear side of the device according to the circuit
diagram. When using forked lugs for screw terminals or in case of direct connections, the screws must be
screwed in so far that the screw heads align with the terminal block before inserting the lugs and wires. A
ring lug must be centered in the connection chamber in such a way that the screw thread fits in the hole of
the lug. The SIPROTEC System Description provides information regarding maximum wire size, torque,
bending radius and cable relief and must be observed.