Appendix
A.8 Settings
SIPROTEC, 7SJ62/64, Manual
C53000-G1140-C207-2, Release date 01.2008
638
4002
46-1 PICKUP
46 Negative Seq
1A
0.10 .. 3.00 A
0.10 A
46-1 Pickup
5A
0.50 .. 15.00 A
0.50 A
4003
46-1 DELAY
46 Negative Seq
0.00 .. 60.00 sec;
∞
1.50 sec
46-1 Time Delay
4004
46-2 PICKUP
46 Negative Seq
1A
0.10 .. 3.00 A
0.50 A
46-2 Pickup
5A
0.50 .. 15.00 A
2.50 A
4005
46-2 DELAY
46 Negative Seq
0.00 .. 60.00 sec;
∞
1.50 sec
46-2 Time Delay
4006
46 IEC CURVE
46 Negative Seq
Normal Inverse
Very Inverse
Extremely Inv.
Extremely Inv.
46 IEC Curve
4007
46 ANSI CURVE
46 Negative Seq
Extremely Inv.
Inverse
Moderately Inv.
Very Inverse
Extremely Inv.
46 ANSI Curve
4008
46-TOC PICKUP
46 Negative Seq
1A
0.10 .. 2.00 A
0.90 A
46-TOC Pickup
5A
0.50 .. 10.00 A
4.50 A
4009
46-TOC TIMEDIAL
46 Negative Seq
0.50 .. 15.00 ;
∞
5.00
46-TOC Time Dial
4010
46-TOC TIMEDIAL
46 Negative Seq
0.05 .. 3.20 sec;
∞
0.50 sec
46-TOC Time Dial
4011
46-TOC RESET
46 Negative Seq
Instantaneous
Disk Emulation
Instantaneous
46-TOC Drop Out
4012A
46 T DROP-OUT
46 Negative Seq
0.00 .. 60.00 sec
0.00 sec
46 Drop-Out Time Delay
4101
FCT 48/66
48/66 Motorprot
OFF
ON
OFF
48 / 66 Motor (Startup Moni-
tor/Counter)
4102
STARTUP CURRENT
48/66 Motorprot
1A
0.50 .. 16.00 A
5.00 A
Startup Current
5A
2.50 .. 80.00 A
25.00 A
4103
STARTUP TIME
48/66 Motorprot
1.0 .. 180.0 sec
10.0 sec
Startup Time
4104
LOCK ROTOR TIME
48/66 Motorprot
0.5 .. 180.0 sec;
∞
2.0 sec
Permissible Locked Rotor Time
4105
STARTUP T WARM
48/66 Motorprot
0.5 .. 180.0 sec;
∞
10.0 sec
Startup Time for warm motor
4106
TEMP.COLD MOTOR
48/66 Motorprot
0 .. 80 %;
∞
25 %
Temperature limit for cold motor
4201
FCT 49
49 Th.Overload
OFF
ON
Alarm Only
OFF
49 Thermal overload protection
4202
49 K-FACTOR
49 Th.Overload
0.10 .. 4.00
1.10
49 K-Factor
4203
TIME CONSTANT
49 Th.Overload
1.0 .. 999.9 min
100.0 min
Time Constant
4204
49
Θ
ALARM
49 Th.Overload
50 .. 100 %
90 %
49 Thermal Alarm Stage
4205
I ALARM
49 Th.Overload
1A
0.10 .. 4.00 A
1.00 A
Current Overload Alarm Setpoint
5A
0.50 .. 20.00 A
5.00 A
4207A
K
τ
-FACTOR
49 Th.Overload
1.0 .. 10.0
1.0
Kt-FACTOR when motor stops
4208A
T EMERGENCY
49 Th.Overload
10 .. 15000 sec
100 sec
Emergency time
4209
49 TEMP. RISE I
49 Th.Overload
40 .. 200 °C
100 °C
49 Temperature rise at rated sec.
curr.
4210
49 TEMP. RISE I
49 Th.Overload
104 .. 392 °F
212 °F
49 Temperature rise at rated sec.
curr.
4301
FCT 66
48/66 Motorprot
OFF
ON
OFF
66 Startup Counter for Motors
4302
IStart/IMOTnom
48/66 Motorprot
1.10 .. 10.00
4.90
I Start / I Motor nominal
4303
T START MAX
48/66 Motorprot
1 .. 320 sec
10 sec
Maximum Permissible Starting
Time
4304
T Equal
48/66 Motorprot
0.0 .. 320.0 min
1.0 min
Temperature Equalizaton Time
4305
I MOTOR NOMINAL
48/66 Motorprot
1A
0.20 .. 1.20 A
1.00 A
Rated Motor Current
5A
1.00 .. 6.00 A
5.00 A
4306
MAX.WARM STARTS
48/66 Motorprot
1 .. 4
2
Maximum Number of Warm
Starts
4307
#COLD-#WARM
48/66 Motorprot
1 .. 2
1
Number of Cold Starts - Warm
Starts
4308
K
τ
at STOP
48/66 Motorprot
0.2 .. 100.0
5.0
Extension of Time Constant at
Stop
4309
K
τ
at RUNNING
48/66 Motorprot
0.2 .. 100.0
2.0
Extension of Time Constant at
Running
4310
T MIN. INHIBIT
48/66 Motorprot
0.2 .. 120.0 min
6.0 min
Minimum Restart Inhibit Time
Addr.
Parameter
Function
C
Setting Options
Default Setting
Comments