Technical Data
4.1 General Device Data
SIPROTEC, 7SJ62/64, Manual
C53000-G1140-C207-2, Release date 01.2008
469
Binary Outputs
1)
FLA = “Full Load Ampere”
2)
High-duty relays are used for the direct activation of motor-driven switches. The high-duty relays operate in
an interlocked mode, i.e. only one binary output of each pair of switches is activated, thus avoiding a short-
circuit of the power supply. When used as a standard relay, only one binary output of a pair can be used.
Permanent operation is not specified.
Output relay for commands/annunciations, alarm relay
*),
, high-duty relay
**) 2)
Number and Information
According to the order variant (allocatable);
values in (): up to release .../DD
Order Variant
NO contact
*
)
NO/NC selectable
*
) high-duty relay
**)
7SJ621*-
6 (8)
3 (1)
–
7SJ622*-
4 (6)
3 (1)
–
7SJ623*-
6 (8)
3 (1)
–
7SJ624*-
4 (6)
3 (1)
–
7SJ640*-
5
1
–
7SJ641*-
12
2
–
7SJ642*-
8
1
4
7SJ645*-
11
1
8
7SJ647*-
21
1
8
Switching Capability MAKE
1000 W/VA
–
Switching Capability BRAKE
30 VA 40 W resistive 25 W
at L/R
≤
50 ms
–
Switching Voltage
250 VDC / VAC
250 VDC / VAC
admissible current per contact (continuous)
5 A
–
admissible current per contact (close and hold)
30 A for 0.5 s (NO contact)
Total current on common path
5 A continuous, 30 A for 0.5 s
–
max. switching capability for 30 s
at 48 V to 250 V
at 24 V
–
1000 W
500 W
Permissible relative closing time
–
1 %
AC Load (it has to be taken into consideration for the dimensions of external circuits)
Value of the ANSI capacitor:
4.70· 10
-9
F
±
20%
Frequency
Impedance
50 Hz
6.77· 10
5
Ω
±
20%
60 Hz
5.64· 10
5
Ω
±
20%
*)
UL–listed with the Following Nominal Values:
120 VAC
Pilot duty, B300
240 VAC
Pilot duty, B300
240 VAC
5 A general purpose
24 VDC
5 A general purpose
48 VDC
0.8 A general purpose
240 VDC
0.1 A general purpose
120 VAC
1/6 hp (4.4 FLA
)
240 VAC
1/2 hp (4.9 FLA
)
**)
UL–listed with the Following Nominal Values:
240 VDC
120 VDC
60 VDC
5.5 FLA
www
. ElectricalPartManuals
. com