Appendix
A.8 Settings
SIPROTEC, 7SJ62/64, Manual
C53000-G1140-C207-2, Release date 01.2008
636
2107
67Nc-TOC T-DIAL
ColdLoadPickup
0.50 .. 15.00 ;
∞
5.00
67Nc-TOC Time Dial
2201
INRUSH REST.
50/51 Overcur.
OFF
ON
OFF
Inrush Restraint
2202
2nd HARMONIC
50/51 Overcur.
10 .. 45 %
15 %
2nd. harmonic in % of fundamen-
tal
2203
CROSS BLOCK
50/51 Overcur.
NO
YES
NO
Cross Block
2204
CROSS BLK TIMER
50/51 Overcur.
0.00 .. 180.00 sec
0.00 sec
Cross Block Time
2205
I Max
50/51 Overcur.
1A
0.30 .. 25.00 A
7.50 A
Maximum Current for Inrush Re-
straint
5A
1.50 .. 125.00 A
37.50 A
2701
50 1Ph
50 1Ph
OFF
ON
OFF
50 1Ph
2702
50 1Ph-2 PICKUP
50 1Ph
1A
0.05 .. 35.00 A;
∞
0.50 A
50 1Ph-2 Pickup
5A
0.25 .. 175.00 A;
∞
2.50 A
2703
50 1Ph-2 PICKUP
50 1Ph
0.003 .. 1.500 A;
∞
0.300 A
50 1Ph-2 Pickup
2704
50 1Ph-2 DELAY
50 1Ph
0.00 .. 60.00 sec;
∞
0.10 sec
50 1Ph-2 Time Delay
2705
50 1Ph-1 PICKUP
50 1Ph
1A
0.05 .. 35.00 A;
∞
0.20 A
50 1Ph-1 Pickup
5A
0.25 .. 175.00 A;
∞
1.00 A
2706
50 1Ph-1 PICKUP
50 1Ph
0.003 .. 1.500 A;
∞
0.100 A
50 1Ph-1 Pickup
2707
50 1Ph-1 DELAY
50 1Ph
0.00 .. 60.00 sec;
∞
0.50 sec
50 1Ph-1 Time Delay
3101
Sens. Gnd Fault
Sens. Gnd Fault
OFF
ON
ON with GF log
Alarm Only
OFF
(Sensitive) Ground Fault
3102
CT Err. I1
Sens. Gnd Fault
0.001 .. 1.600 A
0.050 A
Current I1 for CT Angle Error
3102
CT Err. I1
Sens. Gnd Fault
1A
0.05 .. 35.00 A
1.00 A
Current I1 for CT Angle Error
5A
0.25 .. 175.00 A
5.00 A
3103
CT Err. F1
Sens. Gnd Fault
0.0 .. 5.0 °
0.0 °
CT Angle Error at I1
3104
CT Err. I2
Sens. Gnd Fault
0.001 .. 1.600 A
1.000 A
Current I2 for CT Angle Error
3104
CT Err. I2
Sens. Gnd Fault
1A
0.05 .. 35.00 A
10.00 A
Current I2 for CT Angle Error
5A
0.25 .. 175.00 A
50.00 A
3105
CT Err. F2
Sens. Gnd Fault
0.0 .. 5.0 °
0.0 °
CT Angle Error at I2
3106
VPH MIN
Sens. Gnd Fault
10 .. 100 V
40 V
L-Gnd Voltage of Faulted Phase
Vph Min
3107
VPH MAX
Sens. Gnd Fault
10 .. 100 V
75 V
L-Gnd Voltage of Unfaulted
Phase Vph Max
3108
64-1 VGND
Sens. Gnd Fault
1.8 .. 200.0 V;
∞
40.0 V
64-1 Ground Displacement
Voltage
3109
64-1 VGND
Sens. Gnd Fault
1.8 .. 170.0 V;
∞
40.0 V
64-1 Ground Displacement
Voltage
3110
64-1 VGND
Sens. Gnd Fault
10.0 .. 225.0 V;
∞
70.0 V
64-1 Ground Displacement
Voltage
3111
T-DELAY Pickup
Sens. Gnd Fault
0.04 .. 320.00 sec;
∞
1.00 sec
Time-DELAY Pickup
3112
64-1 DELAY
Sens. Gnd Fault
0.10 .. 40000.00 sec;
∞
10.00 sec
64-1 Time Delay
3113
50Ns-2 PICKUP
Sens. Gnd Fault
0.001 .. 1.500 A
0.300 A
50Ns-2 Pickup
3113
50Ns-2 PICKUP
Sens. Gnd Fault
1A
0.05 .. 35.00 A
10.00 A
50Ns-2 Pickup
5A
0.25 .. 175.00 A
50.00 A
3114
50Ns-2 DELAY
Sens. Gnd Fault
0.00 .. 320.00 sec;
∞
1.00 sec
50Ns-2 Time Delay
3115
67Ns-2 DIRECT
Sens. Gnd Fault
Forward
Reverse
Non-Directional
Forward
67Ns-2 Direction
3117
50Ns-1 PICKUP
Sens. Gnd Fault
0.001 .. 1.500 A
0.100 A
50Ns-1 Pickup
3117
50Ns-1 PICKUP
Sens. Gnd Fault
1A
0.05 .. 35.00 A
2.00 A
50Ns-1 Pickup
5A
0.25 .. 175.00 A
10.00 A
3118
50Ns-1 DELAY
Sens. Gnd Fault
0.00 .. 320.00 sec;
∞
2.00 sec
50Ns-1 Time delay
3119
51Ns PICKUP
Sens. Gnd Fault
0.001 .. 1.400 A
0.100 A
51Ns Pickup
3119
51Ns PICKUP
Sens. Gnd Fault
0.003 .. 0.500 A
0.004 A
51Ns Pickup
3119
51Ns PICKUP
Sens. Gnd Fault
1A
0.05 .. 4.00 A
1.00 A
51Ns Pickup
5A
0.25 .. 20.00 A
5.00 A
Addr.
Parameter
Function
C
Setting Options
Default Setting
Comments