Technical Data
4.24 User-defined Functions (CFC)
SIPROTEC, 7SJ62/64, Manual
C53000-G1140-C207-2, Release date 01.2008
529
Device-specific Limits
Additional Limits
1)
When the limit is exceeded, an error message is output by the device. Consequently, the device starts mon-
itoring. The red ERROR-LED lights up.
2)
The following condition applies for the maximum number of timers: (2 · number of TIMER + number of
TIMER_SHORT) < 30. TIMER and TIMER_SHORT hence share the available timer resources within the
frame of this inequation. The limit does not apply to the LONG_TIMER.
3)
The time values for the blocks TIMER and TIMER_SHORT must not be selected shorter than the time res-
olution of the device, as the blocks will not then start with the starting pulse.
Maximum Number of TICKS in the Task Levels
1)
When the sum of TICKS of all blocks exceeds the limits before-mentioned, an error message is output by
CFC.
Description
Limit
Comments
Maximum number of synchronous
changes of chart inputs per task level
165
When the limit is exceeded, an error message is output by
the device. Consequently, the device starts monitoring. The
red ERROR-LED lights up.
Maximum number of chart outputs per
task level
150
Additional limits
for the following CFC blocks:
Task Level
Maximum Number of Modules in the Task Levels
TIMER
TIMER_SHORT
MW_BEARB
—
PLC1_BEARB
15
30
PLC_BEARB
SFS_BEARB
—
—
Task Level
Limit in TICKS
MW_BEARB (Measured Value Processing )
10000
PLC1_BEARB (Slow PLC Processing )
4000
PLC_BEARB (Fast PLC Processing )
400
SFS_BEARB (Interlocking )
10000