Mounting and Commissioning
3.3 Commissioning
SIPROTEC, 7SC805, Manual
C53000-G1140-C380-1, Release date 05.2014
98
Exiting the Test Mode
To end the System Interface Test, click on
Close
. The device is briefly out of service while the start-up routine
is executed. The dialog box closes.
Test in Command Direction
The information transmitted in command direction must be indicated by the central station. Check whether the
reaction is correct.
3.3.4
Communication Module Configuration
Required Settings in DIGSI 4 and DIGSI Manager
In order that the device can access the new communication module, a change has to be made in the parameter
set within the DIGSI Manager.
In
DIGSI 4 Manager
, select the SIPROTEC device in your project and select the menu item "Edit" - "Object
properties..." to open the
"Properties - SIPROTEC 4 Device"
dialog box (see following Figure ). In the
"Communi-
cation modules"
tab, select the type of communication module or the protocol for
"11. Port F"
using the "L: ..."
button.
Figure 3-22
DIGSI 4: protocol selection (example)