Overcurrent Protection, Phases
Stage with Definite-Time Characteristic Curve
Setting Values
Method of measurement
Fundamental component
RMS value
–
Threshold value
36
1 A @ 100 Irated
0.030 A to 35.000 A
Increments of 0.001 A
5 A @ 100 Irated
0.15 A to 175.00 A
Increments of 0.01 A
Dropout ratio
0.90 to 0.99
Increments of 0.01
Operate delay
0.00 s to 100.00 s
Increments of 0.01 s
Dropout delay
0.00 s to 60.00 s
Increments of 0.01 s
Pickup delay
0.00 s to 60.00 s
Increments of 0.01 s
Dropout
The greater dropout differential (=
| pickup value – dropout value |
) of the following 2 criteria
applies:
Dropout differential derived from the parameter
Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for overcurrent and of 105 % for undercur-
rent functionality.
Minimum absolute dropout differential
Protection-class current transformer
15 mA sec. (I
rated
= 1 A) or
75 mA sec. (I
rated
= 5 A)
Instrument current transformer
0.5 mA sec. (I
rated
= 1 A) or
2.5 mA sec. (I
rated
= 5 A)
Times
Operate time with time delay = 0 ms
Approx. 25 ms + OOT
37
at 50 Hz
Approx. 22 ms + OOT at 60 Hz
Extension of the operate time during operation with
transformer inrush-current detection
Approx. 10 ms
Dropout time
Approx. 20 ms + OOT
Frequency Operating Range
0.9 ≤ f/f
rated
≤ 1.1
According to specified tolerances
10 Hz ≤ f < 0.9 f
rated
1.1 f
rated
< f ≤ 90 Hz
Slightly expanded tolerances
f < 10 Hz
f > 90 Hz
Active
11.15
11.15.1
36
If you have selected the method of measurement = RMS value, do not set the threshold value under 0.1 l
rated,sec
.
37
OOT (Output Operating Time): additional delay of the output medium used, for example 5 ms with fast relays
Technical Data
11.15 Overcurrent Protection, Phases
928
SIPROTEC 5, Low-Impedance Busbar Protection, Manual