[dwocpka4-080213-01.tif, 2, en_US]
Figure 11-14
Operate Curves and Dropout Characteristic Curves According to ANSI/IEEE
Frequency Operating Range
0.9 ≤ f/f
rated
≤ 1.1
According to specified tolerances
10 Hz ≤ f < 0.9 f
rated
1.1 f
rated
< f ≤ 90 Hz
Slightly expanded tolerances
f < 10 Hz
f > 90 Hz
Active
Tolerances
3I0 measured via I4
43
, method of measurement =
fundamental component
1 % of the setting value or 5 mA (I
rated
= 1 A)
or 25 mA (I
rated
= 5 A)
3I0 measured via I4
44
, method of measurement = RMS value
(33 % harmonics, in relation to fundamental component)
Up to 30th harmonic
1 % of the setting value or 5 mA (I
rated
= 1 A)
or 25 mA (I
rated
= 5 A)
Up to 50th harmonic, f
rated
= 50 Hz
3 % of the setting value or 20 mA (I
rated
= 1 A)
or 100 mA (I
rated
= 5 A)
Up to 50th harmonic, f
rated
= 60 Hz
4 % of the setting value or 20 mA (I
rated
= 1 A)
or 100 mA (I
rated
= 5 A)
43
Insignificantly increased tolerances will occur during the calculation of 3I0, maximum factor of 2
44
Insignificantly increased tolerances will occur during the calculation of 3I0, maximum factor of 2
Technical Data
11.16 Overcurrent Protection, Ground
946
SIPROTEC 5, Low-Impedance Busbar Protection, Manual
C53000-G5040-C019-C, Edition 04.2021