Temperature Supervision
Setting Values
Pickup value
-50 °C to 250 °C
-58 °F to 482 °F
Increments of 1°C
Increments of 1°F
Time delay
0 s to 60 s
or ∞
Increments of 1 s
Dropout
Dropout differential
3 °C or 6 °F
Tolerances
Tripping delay
±1 % of the setting value or ±10 ms
Measured temperature value
±0.5 % of the setting value or ±1 °C or ±2 °F
11.35
Technical Data
11.35 Temperature Supervision
988
SIPROTEC 5, Low-Impedance Busbar Protection, Manual
C53000-G5040-C019-C, Edition 04.2021