External Tripping Busbar Section (Direct)
Setting Values
Supervision time
0.06 s to 1.00 s
Increments of 0.01 s
Operate Time
Minimum operate time
Fast relay (type F) approx. 8 ms
Tolerance
Process tolerance for the supervision time
1 % of the setting value or 10 ms
11.8
Technical Data
11.8 External Tripping Busbar Section (Direct)
SIPROTEC 5, Low-Impedance Busbar Protection, Manual
921