Controller Event Tasks
Sources
8
42 | 66
A6V11144326
Type
State (trigger)
Description
Reader Tamper OK An event task is triggered when a reader
returns from a tamper state. Only valid for the
Siemens reader range.
Self Authorization
Granted
Cardholder has self authorized on at Dual
Custody access point.
Valid Daily Code
An event task is triggered when a valid daily
code has been entered at a keypad/reader.
Waiting Dual
Custody Verification
An event task is triggered after the first
cardholder has badged a card, signalling that
the input point is waiting for the second valid
card badge of the config-ured Dual Custody.
Always Set
N/A
This option will set Trigger 1 to be TRUE. This
can be used to generate complex event
triggers, when used in conjunction with the
logical operators and Trigger 2.
Anti Passback Area Area Count Reset
Area count has been reset.
Area Mode Changed Area mode has been changed.
Capacity Empty
The area is vacant.
Capacity Exceeded An event task is triggered when the number of
cardholders in the area exceeds the defined
maximum.
Capacity Full
An event task is triggered when the number of
cardholders currently in the anti-passback area
has reached the programmed capacity.
Capacity Not Empty The area is no longer empty.
Capacity Not Full
The number of cardholders in the area does
not exceed the defined maximum.
Four Eyes Access
Alarm
An event task is triggered when an area under
four eyes control has been violated.
Four Eyes Access
Normal
An event task is triggered when an area under
four eyes control returns to normal.
Workgroup Capacity
Empty
The number of cardholders in the area from a
Workgroup is zero.
Workgroup Capacity
Exceeded
The number of cardholders in the area from a
Workgroup has exceeded the maximum for
that Workgroup.
Workgroup Capacity
Full
The number of cardholders in the area from a
Workgroup has reached the maximum for that
Workgroup.
Workgroup Capacity
Not Empty
The number of cardholders in the area from a
Workgroup is no longer zero.
Workgroup Capacity
Not Full
The number of cardholders in the area from a
Workgroup has not reached the maximum for
that Workgroup.
Card
Access Denied- Hard
perimeter violation
An event task is triggered when an access
attempt has been denied, due to an Anti-
Passback violation in an area configured with
a “Hard” anti
-Passback mode.