Host event tasks
Sources
7
A6V11144326
33 | 66
Source
State (trigger)
Description
Normal
An event task is triggered when the nominated
area point goes into the normal operation state.
Armed
An event task is triggered when an intrusion area
is armed.
Arming Action
Complete
An event task is triggered when an attempt to
arm a dependant intrusion area is complete.
However, other areas, to which the dependant
area belongs, are still unarmed.
Arming failed input X
in alarm
An event task is triggered when an arming
attempt has failed due to an input point in an
alarm state.
Disarmed
An event task is triggered when an area is
unsecured at a Data Entry Terminal.
Part Armed
An event task is triggered when an intrusion area
is part armed.
Part Armed B
An event task is triggered when an intrusion area
is part armed B. (SPC only).
Normal
An event task is triggered when the nominated
area point changes to a normal state.
Intrusion Area
Point Group
Same as Intrusion
Area Points
See “Intrusion Area Point”
Output Point
Lock
An event task is triggered when the nominated
output point is locked.
Note: Locked Temp does not trigger an event
task.
Operator Alarm
An event task is triggered when the nominated
output point goes into alarm.
Operator Alarm
Actioned
An event task is triggered when an alarm,
associated with the nominated output point, is
actioned by an operator.
Operator Alarm Not
Actioned
An event task is triggered when the operator fails
to action an alarm associated with the nominated
output point before the (re-activation) timeout.
Operator Alarm
Timed Out
An event task is triggered when the operator fails
to action the alarm associated with the
nominated output point and the alarm times out.
Operator Normal
An event task is triggered when the nominated
output point changes to a normal state.
Operator Restore
An event task is triggered when the nominated
output point attains ‘Restored’ status.
Operator waiting for
normal
An event task is triggered when a restorable
alarm at the nominated output point has been
actioned but has not returned to its normal state.
Unlock
An event task is triggered when the nominated
output point has been unlocked.
Note: Unlocked Temp does not trigger an event
task.
Output Point
Group
Same as Output
Points
See “Output Point”