Operational Modes
5
22 | 66
A6V11144326
Type
Mode
Description
Input/Outpu
t
Passback
The input is in alarm state until the passback
button has been pressed and the input delay is
activated. Triggering passback unlocks the door
latch.
Passback No Message
The input is in alarm state until the passback
button has been pressed and the input delay is
activated. No passback message is reported
back to the system. The latch is not
automatically unlocked. Triggering passback
unlocks the door latch.
Passback No Report
–
Lock not activated
The input is in alarm state until the passback
button has been pressed and the input delay is
activated. No passback message is reported
back to the system. Triggering passback does
not unlock the door latch.
Passback Report
–
Lock
not activated
The input is in alarm state until the passback
button has been pressed and the input delay is
activated. Triggering passback does not unlock
the door latch.
Input Disabled
Disables the input point.
Door Frame Auto Pre-
Alarm
A Pre-Alarm will sound before the main Door
Held Alarm. The Pre-Alarm will not be
registered on the Alarm Queue.
If the door is not returned to a normal state
within the Pre-Alarm time period, the Door Held
Alarm will sound and will be registered in the
alarm queue.
The Door Held Alarm will auto-matically stop
when the door returns to a normal state.
Door Frame Dual Timer
Defines the input point as a door contact sensor
that monitors the open or closed state of the
door. The input point will use both the Pre-
Alarm Delay and Input Delay times when
sending alarms.
Door Frame Held Only
In case when the door has a reader on the
outside but no reader (and no passback) on the
inside, this mode holds an open door virtually
for the Input Delay time duration set by the user
and prevents reporting the event as “door
-
force”.
Door Frame Manual Pre-
Alarm
A Pre-Alarm will sound before the main Door
Held Alarm. The Pre- Alarm will not be
registered on the Alarm Queue.
If the door is not returned to a normal state
within the Pre-Alarm time period, the Door Held
Alarm will sound and will be registered in the
alarm queue.
The Door Held will stop only when the door is
returned to a normal state and the alarm has
been acknowledged.
Door Frame Sensor
Defines the input point as a door contact sensor
that monitors the open or closed state of the
door.
Alarm/Normal
Both changes to alarm and normal states are
reported to the system.