Preparing for Operation
73
SIPART PS2 Manual
A5E00074631--06
3.6.1 Preparations for linear actuators
1. Assemble the positioner with the appropriate mounting kit
(see chapter 3.3.3, page 39).
.
NOTE
Particularly important is the position of the transmission ratio selec-
tor (8, figure 2-2, page 17) in the positioner:
Stroke
Lever
Position of the transmission ratio
selector
5 to 20 mm
short
33
°
(i.e. down)
25 to 35 mm
short
90
°
(i.e. up)
40 to 130 mm
long
90
°
(i.e. up)
2. Push the carrier pin (4, figure 3-7 (page 51) 2) onto the lever
(6, figure 3-7, 2) to the scale position corresponding to the rated
stroke or next highest position and screw the carrier pin tight with
the nut (18, figure 3-7, 2).
3. Connect the actuator and the positioner with the pneumatic lines
and supply pneumatic power to the positioner (figure 2-4 and 2-5,
page 19).
4. Connect a suitable current or voltage source (see figure 3-13,
page 59 and figure 3-20, page 63).
5. The positioner is now in the operating mode “
P-manual opera-
tion
” The current potentiometer voltage (P) is displayed in percent
in the top line of the display, e.g.: “
P12.3
”, and “
NOINI
” flashes in
the bottom line:
6. Check the free running of the mechanics in the whole actuating
range by moving the actuator with the keys
and
and driving
to the respective end position.
.
NOTE
You can move the actuator quickly by pressing the other direction key
additionally whilst keeping the direction key selected first pressed.
7. Now move the actuator to the horizontal position of the lever.
A value between
P48.0
and
P52.0
should be visible in the display.
If this is not the case, adjust the friction clutch (8, figure 2-11, page
28 or in frameproof enclosure 8, figure 2-12, page 31) until “
P50.0
”
is displayed with a horizontal lever. The more accurately you hit
this value, the more exactly the positioner can determine the path.
Summary of Contents for SIPART PS2 6DR50 Series
Page 40: ...Design and Functional Principle 40 SIPART PS2 Manual A5E00074631 06 Table 2 1 Scopetuator ...
Page 88: ...Preparing for Operation 88 SIPART PS2 Manual A5E00074631 06 ...
Page 96: ...Operation 96 SIPART PS2 Manual A5E00074631 06 Figure 4 6 Parameter table of the positioner ...
Page 144: ...Operation 144 SIPART PS2 Manual A5E00074631 06 ...
Page 160: ...Appendix 160 SIPART PS2 Manual A5E00074631 06 ...