Operation
123
SIPART PS2 Manual
A5E00074631--06
No.
Reset
possible
Unit
Values than
can be
indicated
Meaning
Abbre-
viation
21
P100
P
otentiometer value upper stop (
100
%)
0.0 to 100.0
%
22
IMPUP
Pulse length up (
Imp
ulse Length
Up
)
2 to 160
ms
23
IMPDN
Pulse length down (
Imp
ulse Length
D
ow
n
)
2 to 160
ms
24
DBUP
Dead zone up (
D
ead
B
and
Up
)
0.1 to 10.0
%
25
DBDN
Dead zone down (
D
ead
B
and
D
ow
n
)
0.1 to 10.0
%
26
SSUP
Short step zone up (
S
hort
S
tep Zone
Up
)
0.1 to 100.0
%
27
SSDN
Short step zone down (
S
hort
S
tep Zone
D
ow
n
)
0.1 to 100.0
%
28
TEMP
Current
temp
erature
--40 to 85
_
C
29
TMIN
Min
imum
t
emperature (“min/max pointer”)
--40 to 85
_
C
30
TMAX
Max
imum
t
emperature (“min/max pointer”)
--40 to 85
_
C
31
T1
Number of operating hours in
t
emperature range
1
0 to 4.29E9
hours
32
T2
Number of operating hours in
t
emperature range
2
0 to 4.29E9
hours
33
T3
Number of operating hours in
t
emperature range
3
0 to 4.29E9
hours
34
T4
Number of operating hours in
t
emperature range
4
0 to 4.29E9
hours
35
T5
Number of operating hours in
t
emperature range
5
0 to 4.29E9
hours
36
T6
Number of operating hours in
t
emperature range
6
0 to 4.29E9
hours
37
T7
Number of operating hours in
t
emperature range
7
0 to 4.29E9
hours
38
T8
Number of operating hours in
t
emperature range
8
0 to 4.29E9
hours
39
T9
Number of operating hours in
t
emperature range
9
0 to 4.29E9
hours
40
VENT1
Number of switching operations pilot
val
lve
1
0 to 4.29E9
--
41
VENT2
Number of switching operations pilot
val
lve
2
0 to 4.29E9
--
42
STORE
Save current values as “last maintenance”
(press increment button for 5s) (
Store
)
--
--
43
PRUP
Prediction up
1 to 40
--
44
PRDN
Prediction down
1 to 40
--
45
WT00
Number of operating hours in actuating range WT00
0 to 4.29E9
hours
x
46
WT05
Number of operating hours in actuating range WT05
0 to 4.29E9
hours
x
47
WT10
Number of operating hours in actuating range WT10
0 to 4.29E9
hours
x
48
WT30
Number of operating hours in actuating range WT30
0 to 4.29E9
hours
x
49
WT50
Number of operating hours in actuating range WT50
0 to 4.29E9
hours
x
50
WT70
Number of operating hours in actuating range WT70
0 to 4.29E9
hours
x
51
WT90
Number of operating hours in actuating range WT90
0 to 4.29E9
hours
x
52
WT95
Number of operating hours in actuating range WT95
0 to 4.29E9
hours
x
53
mA
Setpoint current
0.0 to 20.0
mA
Table 4-1
Overview of diagnosis values
4.5.2 Meaning of the diagnosis values
Number of strokes
During operation, the actuator movements are added up and can be
read off here as the number of strokes. Unit: 100% strokes, i.e. the
path between 0 and 100 % and back. The value is written into a
non-volatile memory every 15 minutes. It can be set to zero with the
increment button
.
Number of changes of direction
1 STRKS
2 CHDIR
Summary of Contents for SIPART PS2 6DR50 Series
Page 40: ...Design and Functional Principle 40 SIPART PS2 Manual A5E00074631 06 Table 2 1 Scopetuator ...