Design and Functional Principle
29
SIPART PS2 Manual
A5E00074631--06
2.7.2 Installation of options modules in explosion proof version
The following option modules are available for the positioner in the ex-
plosion-proof version:
--
Iy
-module
-- Alarm module
The options modules are protected and mechanically fixed by a module
cover ((1), see figure 2-12, page 31).
.
NOTE
The housing must be opened to install the options modules. The
degree of protection IP66/NEMA4x is not guaranteed as long as the
positioner is open.
!
WARNING
In areas in which the atmosphere may be potentially explosive, the
explosion-proof positioner may only be supplied with electrical auxiliary
power when the housing is closed and when built-in, approved elec-
tronics are used.
The feed-though openings for the electronic connections must be
sealed with EEX-d certified cable glands or EEx-d certified plugs or
an ignition lock must be mounted at a maximum distance of 46 cm
(18 inches) when using the “conduit”-system.
See figure 2-12, page 31. Disconnect or isolate the power supply
cables first.
To open the positioner, the safety catch (12) must be opened and the
screw-on cover unscrewed.
After loosening the four fixing screws (13.1) the complete rack (13) can
be removed. The actuator may have to be turned so that the clutch can
be easily disengaged.
Remove the module cover (1). To do this, the two screws (1.1) must be
removed with a screwdriver.
Installation
Open the
positioner
Summary of Contents for SIPART PS2 6DR50 Series
Page 40: ...Design and Functional Principle 40 SIPART PS2 Manual A5E00074631 06 Table 2 1 Scopetuator ...
Page 88: ...Preparing for Operation 88 SIPART PS2 Manual A5E00074631 06 ...
Page 96: ...Operation 96 SIPART PS2 Manual A5E00074631 06 Figure 4 6 Parameter table of the positioner ...
Page 144: ...Operation 144 SIPART PS2 Manual A5E00074631 06 ...
Page 160: ...Appendix 160 SIPART PS2 Manual A5E00074631 06 ...