Installation
40
9229 0025 176 0A
2019-08-05
Mounting the system-side separating shells
System-side separating shells (47) can be used to insulate the individual poles from
each other if there is restricted terminal space.
When using system-side separating shells (47), you can use main conductors with
a max. diameter or cross-section of 60 mm.
• Slide separating shells (47) onto previously mounted threaded rods of main con-
ductors (connecting the main conductors, see “Connecting the main conductor”
page 50).
• Place separating shell (47) onto the pole shell (46) and engage into the guide.
• Engage the hooks by hand if necessary.
• Place upper separating shell (47) at a slight angle from above onto the rib
(arrow A) and press against the pole shell (46) until it engages audibly.
• Press lower separating shell (47) horizontally against the pole shell (46) until it
engages audibly.
Fig. 53
Up to 17.5 kV, mounting separating shells
Fig. 54
Up to 17.5 kV, engaging separating shells
Fig. 55
24 kV, mounting separating shells
Fig. 56
24 kV, engaging separating shells