SIMPRO-100
SIMPRO-PC Compatibility Features
D
PRIM-2400C
199
If the relay is not equipped with internal or
external RTD inputs, the RTD labels are replaced
with “*”. If the relay is equipped with RTD inputs,
the RTD locations (BRG, WDG, etc.) are setting
dependent. If Fahrenheit is the designated
temperature scale, the temperature designator
(C) is replaced with (F)
where:
•
"THM CAP(%)" is the thermal model
thermal capacity used in percent.
•
"RTD TC(%)" is the RTD estimated
thermal capacity used in percent.
•
"CALC TIME" is the calculated time to
thermal trip in seconds.
•
"MINUTES" is the number of minutes
since the last motor start.
•
"STARTS" is the number of motor starts in
the past hour.
D.6
CSTATUS Command
Display status data in compressed ASCII format
by typing
CST <CR>
. The relay replaces the
items in italics with the actual relay data.
The SIMPRO-100 Relay sends:
where:
•
"xxxx" are the data values corresponding
to the first line labels
•
"zzzz" is a message saying whether the
relay is “ENABLED” or “DISABLED"
•
"yyyy" is the 4-byte hex ASCII
representation of the checksum
In relays where voltages are not supported, “VA”,
“VB”,”VC”, and “N” are reported as “*”.
D.7
CHISTORY
Command
Display history data in compressed ASCII format
by typing:
CHI <CR>
The relay replaces the items in italics with the
actual relay data.
The SIMPRO-100 Relay sends:
(the second line is then repeated for each record)
where:
•
"xxxx" are the data values corresponding
to the first line labels
•
"yyyy" is the 4-byte hex ASCII
representation of the checksum
•
"THM CAP(%)" is the thermal model
thermal capacity used in percent
Summary of Contents for SIMPRO-100
Page 1: ...SIMPRO 100 Motor Protection Relay Instruction Manual Document No PRIM 2400C ...
Page 12: ...Contents SIMPRO 100 x PRIM 2400C ...
Page 16: ...Contents SIMPRO 100 xiv PRIM 2400C ...
Page 42: ...3 SIMPRO PC Software SIMPRO 100 40 PRIM 2400C ...
Page 100: ...6 ASCII Serial Port Operation SIMPRO 100 98 PRIM 2400C ...
Page 127: ...SIMPRO 100 Event Analysis 9 PRIM 2400C 125 Figure 9 2 Example SER Report ...
Page 136: ...10 Maintenance Troubleshooting SIMPRO 100 134 PRIM 2400C ...
Page 138: ...A Firmware Versions SIMPRO 100 136 PRIM 2400C ...
Page 206: ...D SIMPRO PC Compatibility Features SIMPRO 100 204 PRIM 2400C ...
Page 214: ...E Motor Thermal Element SIMPRO 100 212 PRIM 2400C ...
Page 230: ...F SIMPRO 100 Relay Settings Sheets SIMPRO 100 228 PRIM 2400C ...
Page 239: ......