![Siemens SIMOCODE pro Programming And Operating Manual Download Page 244](http://html.mh-extra.com/html/siemens/simocode-pro/simocode-pro_programming-and-operating-manual_1265395244.webp)
Parameter
A.3 Block parameter MMOprtn
SIMOCODE pro PCS 7 Library V9.0
244
Programming and Operating Manual, 06/2017, A5E40899442002A/RS-AA/001
A.3
Block parameter MMOprtn
Input parameters
Table A- 11 Input parameter MMOprtn
Parameter
Data format
Default setting
Meaning
Mode
DWORD
16#8000FFFF
OMODE
information of MOD_SWT
RackF
STRUCT
•
Value: BOOL
•
ST: BYTE
–
•
0
•
16#80
1 = Rack failure information from MMDiag
ModF
STRUCT
•
Value: BOOL
•
ST: BYTE
–
•
0
•
16#80
1 = Module failure information from
Slv_Typ
BOOL
FALSE
0 = PROFIBUS
1 = PROFINET
DAddr
INT
0
Diagnostics address of SIMOCODE
LAddr
INT
0
Logical address of SIMOCODE
RdWrEn
BOOL
TRUE
1 = Enable read/write data record
RdDataLi
STRUCT
•
Value: BOOL
•
ST: BYTE
–
•
0
•
16#80
Input 0->1 = Read data record via Link or SFC
RdDataOp
BOOL
FALSE
1 = Read data from datasets
ModLiOp
STRUCT
•
Value: BOOL
•
ST: BYTE
–
•
0
•
16#80
Input to Auto/Manual Commands
0 = Manual
1 = Link/Auto
AutModOp
BOOL
FALSE
1 = AUTO mode via operator
ManModOp
BOOL
TRUE
1 = MANUAL mode via OS operator
AutModLi
STRUCT
•
Value: BOOL
•
ST: BYTE
–
•
0
•
16#80
1 = AUTO mode via Link or SFC
ManModLi
STRUCT
•
Value: BOOL
•
ST: BYTE
–
•
0
•
16#80
1 = MANUAL mode via Link or SFC
Diag_Sts
SMCSTATUS
–
SIMOCODE diagnostics status information from
MMDiag
Diag_Evt
SMCEVNT
–
SIMOCODE diagnostics event information from
MMDiag
Diag_Wrn
SMCWRNG
–
SIMOCODE diagnostics warning information from
MMDiag
Diag_Trp
SMCTRP
–
SIMOCODE diagnostics trip information from
MMDiag