Description of the blocks
4.7 MMRevDhl motor block
SIMOCODE pro PCS 7 Library V9.0
Programming and Operating Manual, 06/2017, A5E40899442002A/RS-AA/001
221
Status4
Table 4- 107 Status4 – MMRevDhl
Status4
bit
Description
0
"Permission Forward" button is enabled
1
"Permission Reverse" button is enabled
2
"Interlock Forward" button is enabled
3
"Interlock Reverse" button is enabled
4
"Protect Forward" button is enabled
5
"Protect Reverse" button is enabled
6
1 = Permission Reverse is active
7
1 = Interlock Reverse is active
8
1 = Protect Reverse is active
9
FwdChnST is connected
10
RevChnST is connected
11
FwdChnST is connected
12
RevChnST is connected
13...16
Not used
17
Monitor
18...31
Not used
4.7.23
Restart lock after changing direction of rotation or switching off the motor using
idle time
Use the input parameter
IdleTime
to enter a restart lock for changing the direction of rotation
or restarting the motor. Use the
Feature
Bit 'Enabling direct changeover between forward
and reverse' (Page 83) to define how switchover is to be performed. When the "Stop"
command is given, the motor goes immediately into "Stop" mode, and
IdleTime
starts after
the feedback (
FbkFwd
and
FbkRev
= 0) is given. The motor cannot be started again until the
IdleTime
has expired. For example, the
IdleTime
can be changed (increase/decrease) when
the block has entered
IdleTime
from the "Stop" mode.
The
IdleTime
parameter can be set independently of the
MonTiDynamic
parameter.
Note
Idle time is not applicable during speed transitions.