![Siemens SIMOCODE pro Programming And Operating Manual Download Page 199](http://html.mh-extra.com/html/siemens/simocode-pro/simocode-pro_programming-and-operating-manual_1265395199.webp)
Description of the blocks
4.7 MMRevDhl motor block
SIMOCODE pro PCS 7 Library V9.0
Programming and Operating Manual, 06/2017, A5E40899442002A/RS-AA/001
199
Conditions for changing the mode
Table 4- 93 Conditions for changing the mode
No.
Conditions
①
MANUAL (ON) → Out of service (Oos)
•
Via faceplate
(OosOp = 1)
if
ModLiOp = 0
or
•
on an edge transition
0 → 1
from
OosLi,
if
Feature.Bit1 = 1
(response for Out of
service mode)
②
Out of service (Oos) → MANUAL (ON)
Via faceplate
(ManModOp = 1)
③
Local → MANUAL
•
Via faceplate
(ManModOp = 1)
if
ModLiOp = 0
and
LocalSetting = 3
or
LocalSetting
= 4
or
•
via
LocalLi = 0
, if
LocalSetting = 1, LocalSetting = 2
④
AUTOMATIC → MANUAL
•
Via faceplate
(ManModOp = 1)
if
ModLiOp = 0
or
•
via
ManModLi = 1
if
ModLiOp = 1
and
Feature.Bit4 =
0 (pushbutton mode) or
•
via
AutModLi = 0
if
ModLiOp = 1
and
Feature.Bit4 =
1 (switch mode)
⑤
MANUAL → AUTOMATIC
•
Via faceplate
(AutModOp = 1)
if
ModLiOp = 0
or
•
via
AutModLi = 1
if
ModLiOp = 1
⑥
Manual → Local
•
Via faceplate
(LocalOp = 1)
if
ModLiOp = 0
and
LocalSetting = 3
or
LocalSetting =
4
or
•
via
LocalLi = 1
, if
LocalSetting = 1,
LocalSetting = 2
⑦
AUTOMATIC → Local
•
Via faceplate
(LocalOp = 1)
if
ModLiOp = 0
and
LocalSetting = 3
or
LocalSetting =
4
or
•
via
LocalLi = 1
, if
LocalSetting = 1, LocalSetting = 2
⑧
Local → AUTOMATIC
•
Via faceplate
(AutModOp = 1)
if
ModLiOp = 0
and
LocalSetting = 3
or
LocalSetting
= 4
or
•
via
LocalLi = 0
, if
LocalSetting = 1, LocalSetting = 2
If
ModLiOp = 1
, the enabled operations for all mode changes will be deactivated.
If the block is in local mode, no other mode can be activated for it.