Description of the blocks
4.6 Block for timestamping MMLog
SIMOCODE pro PCS 7 Library V9.0
192
Programming and Operating Manual, 06/2017, A5E40899442002A/RS-AA/001
4.6.7
Driver generator
The "Generate Module Driver" function automatically inserts the MMLog block into the
following organization blocks within the run sequence:
●
OB40 (process alarm)
●
OB100 (warm restart)
The
DAddr
input is parameterized via the information from the HW Config.
4.6.8
Start-up characteristics
In OB100, the identifier for "Start up" is entered in output
OMODE
(
OMODE = 16#xx01xxxx
).
The alarm messages are suppressed in the OB100 for the
RunUpCyc
no. of times.
Acknowledge the errors
GrpErr
,
RackF_Act
,
ModF_Act
,
Rack1Err
, and
Rack2Err
.
4.6.9
Status information
The status information is communicated to WinCC for display in the faceplates.
Table 4- 91 Status information – MMLog
Status1
Bit
Description
0
Occupied
1
BatchEn
2
SIMOCODE Device Class
3
1 = Oos Mode
4
OosLi Active
5
0 = Default read logbook
1 =Suppress logbook
6
0 = On mode
1 = Local mode
7
Message Lock
8
Time stamp Active
9
Logbook error 1 Type
10
Logbook error 2 Type
11
Logbook error 3 Type
12
Logbook error 4 Type
13
Logbook error 5 Type
14
Logbook error 6 Type
15
Logbook error 7 Type
16
Logbook error 8 Type
17
Logbook error 9 Type