Useful information
4.1
Time stamping
SIMOCODE pro V can time stamp digital signals. In this case, any change of signal
is recorded.
It is possible to log the following signals, for instance for statistical analysis:
•
automatic reversal run (output of Timer 1)
•
Current lower limit in conveying direction reached (output of limit monitor 2)
•
Current upper limit in conveying direction reached (output of limit monitor 3)
•
Cos φ lower limit in conveying direction reached (output of limit monitor 4)
The example project does not receive a time stamp for the aforementioned signals
because:
•
Time stamping is not part of the core contents of this application example.
•
Time stamping is only available with the PROFIBUS variant of the SIMOCODE
pro V.
•
Time stamping requires that the DP master in use supports the functions for
time synchronization via PROFIBUS (see chapter entitled "Time stamping" in
the manual
describes the parameterization of the SIMOCODE device.