![Siemens SIMOCODE pro V Manual Download Page 49](http://html.mh-extra.com/html/siemens/simocode-pro-v/simocode-pro-v_manual_385613049.webp)
3 Engineering
Blocking Protection for Pumps with SIMOCODE pro V
Article ID: 109478058, V2.0, 09/2020
49
©
S
iem
e
n
s A
G
2020
A
ll r
igh
ts
re
se
rv
e
d
Signal conditioning
1. Define the following parameters under "Logic modules > Signal conditioning >
Signal conditioning 1".
–
Type: "edge rising with memory"
–
Input: Control command "ON>"
–
Reset: Output TT 1 (truth table 1)
2. Define the following parameters under "Logic modules > Signal conditioning >
Signal conditioning 2".
–
Type: "inverting"
–
Input: Output Timer 2
3. Define the following parameters under "Logic modules > Signal conditioning >
Signal conditioning 3".
–
Type: "edge rising with memory"
–
Input: OP button 1
–
Reset: Output Counter 3