2 Operating principle
Blocking Protection for Pumps with SIMOCODE pro V
Article ID: 109478058, V2.0, 09/2020
12
©
S
iem
e
n
s A
G
2020
A
ll r
igh
ts
re
se
rv
e
d
2.2
Explanation of the logic
2.2.1
Embedding
If you parameterize the preconfigured application "Reversing starter" under
"Parameters > Configuration", the function blocks "Control station" and
"Protection/Control" are interconnected by default as per
Figure 2-7
To embed the logic for blockage prevention, the interconnection of the ON
commands has been separated. The authorized control commands "ON<", "ON>"
and "OFF" from "Control station" are fed into the logic as inputs (marked in green in
). The outputs of the logic are interconnected to the "ON"
plugs of "Protection/Control" (marked in orange in
). The
enabled command "OFF" from Control station remains connected with the "OFF"
plug of "Protection/Control".
Figure 2-8