3 Engineering
Blocking Protection for Pumps with SIMOCODE pro V
Article ID: 109478058, V2.0, 09/2020
48
©
S
iem
e
n
s A
G
2020
A
ll r
igh
ts
re
se
rv
e
d
Timer
1. Define the following parameters under "Logic modules > Timer > Timer 1".
–
Type: "with opening delay"
–
Limit value: 30.0
–
Input: Output 1 TT 9 (truth table 9)
–
Reset: Output TT 8 (truth table 8)
2. Define the following parameters under "Logic modules > Timer > Timer 2".
–
Type: "with closing delay"
–
Limit value: 3600.0
–
Input: Output signal conditioning 2
–
Reset: Output Timer 1