3 Engineering
Blocking Protection for Pumps with SIMOCODE pro V
Article ID: 109478058, V2.0, 09/2020
50
©
S
iem
e
n
s A
G
2020
A
ll r
igh
ts
re
se
rv
e
d
Limit monitor
1. Under "Logic modules > Limit monitor > Limit monitor 1", parameterize the
"Limit monitor" function block for the current upper limit in reverse direction.
The limit monitor should always be active ("always (on)")
The limit should be specified in %, based on the motor current at the input
plug. If necessary, assign a label.