2-18
SIMATIC TD 200 Operator Interface
C79000-G7076-C272-01
Viewing the TD 200 Parameter Block and Messages
The TD 200 Configuration Wizard creates a data block containing the TD 200
parameter block and messages. You can open the data block editor to view the
TD 200 parameter block and messages that were formatted by the wizard.
Figure 2-17 shows the data block for the example in this chapter.
Data Block
DB
// BEGIN TD200_BLOCK 0
// (Comments within this block should not be edited or removed)
VB0
‘TD’
// TD 200 Identification
VB2
16#10
// Set Language to English, set Update to As fast as possible
VB3
16#F1
// Set the display to 40 character mode; Up key V3.2; Down key V3.3
VB4
3
// Set the number of messages
VB5
0
// Set the Function Keys notification bits to M0.0 - M0
VW6
40
// Set the starting address for messages to VW40
VW8
14
// Set the starting address for message enable bits to VW14
VW10
1111
// Global Password
VW12
1
// Character Set = Latin1
// MESSAGE 1
// Message Enable Bit V14.7
VB40
‘PRESS F1 TO DISPLAY THE NEXT MESSAGE ...’
// MESSAGE 2
// Message Enable Bit V14.6
VB80
‘PREV. SETPOINT: ’
VB96
16#00
// No Edit; No Acknowledgement; No Password
VB97
16#11
// Signed Word; 1 Digits to the right of the decimal;
VW98
16#00
// Embedded Data Value: Move data for display here.
VB100 ‘NEW SETPOINT: ’
VB114 16#18
// Edit Notification V114.2; No Acknowledgement; Edit Requires Passw
VB115 16#51
// Real Double Word; 1 Digits to the right of the decimal;
VD116 16#0000
// Embedded Data Value: Move data for display here.
// MESSAGE 3
// Message Enable Bit V14.5
VB120 ‘ACKNOWLEDGE MESSAGE BY PRESSING ENTER:’
VB158 16#01
// No Edit; Acknowledgement Notification V158.1; No Password
VB159 16#00
// No Data; 0 Digits to the right of the decimal;
// END TD200_BLOCK 0
Figure 2-17 Data Block Editor Showing a Sample TD 200 Parameter Block
Configuring the TD 200
Summary of Contents for SIMATIC TD 200
Page 22: ...1 12 SIMATIC TD 200 Operator Interface C79000 G7076 C272 01 Product Overview and Installation ...
Page 84: ...A 12 SIMATIC TD 200 Operator Interface C79000 G7076 C272 01 Specifications and Reference ...
Page 94: ...B 10 SIMATIC TD 200 Operator Interface C79000 G7076 C272 01 Multiple CPU Configurations ...
Page 126: ...E 6 SIMATIC TD 200 Operator Interface C79000 G7076 C272 01 Modifying a TD 200 Configuration ...