3-9
SIMATIC TD 200 Operator Interface
C79000-G7076-C272-01
3.5
Forcing I/O
The Force I/O menu is only available if the force-menu enable is set in the TD 200
configuration that is stored in the CPU. The Force I/O menu allows you to force
inputs, force outputs, or unforce all inputs and outputs.
In the S7-200 CPU, you can establish password protection for the force I/O
function. The TD 200 reads the password protection level from the CPU. If the
force function is password protected, the TD 200 asks you to enter the CPU
password.
Note
The CPU password restricts editing of the force information in the S7-200 CPU.
This password is different from the password protection offered by the TD 200,
which restricts the editing of variables that are embedded in a message.
Accessing the Menu
To access the Force I/O menu, perform the following steps.
Key
Action
Display
1.
ESC
The TD 200 enters the Menu mode.
VIEW MESSAGES
MENU MODE:
2.
The TD 200 scrolls down the menu
options two times.
FORCE I/O
MENU MODE:
3.
ENTER
The TD 200 enters the Force I/O
menu. If a force function is password
protected, the TD 200 displays the
following.
PASSWORD ********
PASSWORD REQUIRED
Note
Pressing ESC at any time while you are forcing I/O returns you to the Display
Message mode. The TD 200 automatically returns to the Display Message mode
after one minute if no keys are pressed.
Operating the TD 200
Summary of Contents for SIMATIC TD 200
Page 22: ...1 12 SIMATIC TD 200 Operator Interface C79000 G7076 C272 01 Product Overview and Installation ...
Page 84: ...A 12 SIMATIC TD 200 Operator Interface C79000 G7076 C272 01 Specifications and Reference ...
Page 94: ...B 10 SIMATIC TD 200 Operator Interface C79000 G7076 C272 01 Multiple CPU Configurations ...
Page 126: ...E 6 SIMATIC TD 200 Operator Interface C79000 G7076 C272 01 Modifying a TD 200 Configuration ...