Test functions
12.1 Test functions
S7-1500R/H redundant system
284
System Manual, 10/2018, A5E41814787-AA
Testing with watch tables
The following functions are available in the watch table:
●
Monitoring of tags
Using watch tables, you can monitor the actual values of the individual tags of a CPU
user program.
–
On the PG/PC
–
On the display of the CPU
Please note the following requirement for displaying the tag values on the CPU display:
You must specify a symbolic name for each tag in the "Name" column of the force table.
You monitor the following operand areas:
–
Inputs and outputs (process image) and bit memory
–
Contents of data blocks
–
Peripheral inputs and peripheral outputs
–
Timers and counters
●
Modifying tags
You use this function to assign values to the individual tags of a user program or a CPU
on the PG/PC. Modifying is also possible with Test with program status.
The following operand areas are modifiable:
–
Inputs and outputs (process image) and bit memory
–
Contents of data blocks
–
Peripheral inputs and peripheral outputs (for example, %I0.0:P, %Q0.0:P)
–
Timers and counters