Technical specifications
13.4 Mechanical and climatic ambient conditions
S7-1500R/H redundant system
System Manual, 10/2018, A5E41814787-AA
299
13.4
Mechanical and climatic ambient conditions
Operating conditions
The S7-1500R/H redundant system is designed for stationary use in weather-proof locations.
The operating conditions are based on the requirements of DIN IEC 60721-3-3:
●
Class 3M3 (mechanical requirements)
●
Class 3K3 (climatic requirements)
Test of mechanical ambient conditions
The table below provides important information with respect to the type and scope of the test
of ambient mechanical conditions.
Table 13- 7 Test of mechanical ambient conditions
Condition tested
Test Standard
Comment
Vibration
Vibration test accord-
ing to IEC 60068-2-6
(Sinus)
Type of oscillation: Frequency sweeps with a rate of change of 1 oc-
tave/minute.
5 Hz
≤
f
≤
8.4 Hz, constant amplitude 7 mm
8.4 Hz
≤
f
≤
150 Hz, constant acceleration 2 g
Duration of oscillation: 10 frequency sweeps per axis, along each of the 3
mutually perpendicular axes
Shock
Shock, tested accord-
ing to IEC 60068-2-27
Type of shock: Half-sine
Shock intensity: 15 g max., duration 11 ms
Direction of shock: 3 shocks each in (+/-) direction, along each of the 3
mutually perpendicular axes
Continuous shock
Shock, tested accord-
ing to IEC 60068-2-27
Type of shock: Half-sine
Shock intensity: 250 m/s
2
peak value, 6 ms duration
Direction of shock: 1000 shocks each in (+/-) direction, along each of the
3 mutually perpendicular axes
Reduction of vibrations
If the S7-1500R/H redundant system is exposed to severe shock or vibration, take
appropriate measures to reduce the acceleration or the amplitude.
We recommend installing the S7-1500R/H redundant system on damping materials (for
example, rubber-bonded metal mounting).